Specifications
3. INITIALIZE COMMUNICATION DATA
IMR01H03-E4
33
!"Communication identifier list
For details on the structure of communication data, see Communication Instruction
Manual (IMR01H02-E
#
).
Name Iden-
tifier
No. of
digits
Data range Factory set
value
Attri-
bute
CH
STOP display
selection
DX 1 0: It makes display “STOP” in
PV display.
1: It makes display “STOP” in
SV display.
0R/W−
Input type
selection
XI 6 0 to 16 (See P. 18)Note 1R/W×
Display unit
selection
PU 10: °C
1: °F
0R/W×
Decimal point
position setting
XU 1 0: No digit below decimal point
1: 1 digit below decimal point
2: 2 digits below decimal point
3: 3 digits below decimal point
Note 2 R/W ×
Setting limiter
[high limit] setting
XV 6 Within input range. Note 3 R/W ×
Setting limiter
[low limit] setting
XW See 4. INPUT RANGE
TABLES (P. 55)
CT ratio 1
1
selection
XR 6 0 to 9999 (See P. 20)Note 4R/W×
CT ratio 2
1, 2
selection
XS
1
When selecting CT ratio 1 or 2, as a channel number specified after the identifier, specify the
channel number corresponding to the CT ratio selection.
For the CT ratio selection channel number, see the 2.4 F22 Current Transformer (CT)
Input Specification (P. 20).
2
Do not use CT ratio 2 for the MA901.
Note 1 Factory set value varies depending on the input type.
Note 2 Factory set value varies depending on the instrument specification. However, factory set value
of a case of voltage input is 1.
Note 3 Factory set value varies depending on the instrument specification. However, factory set value
of a case of voltage input is 100.0 (high limit) and 0.0 (low limit).
Note 4 CTL-6-P-N: 800
CTL-12-S56-10L-N: 1000
Continued on the next page.