Specifications

32
IMR01H03-E4
3. INITIALIZE COMMUNICATION DATA
3.1 RKC Communication Protocol
!"
!"!"
!"
Reference to communication identifier list
(1) (2) (3) (4) (5) (6) (7)
Name Iden-
tifier
No. of
digits
Data range Factory set
value
Attri-
bute
CH
STOP display
selection
DX 1 0: It makes display “STOP” in
PV display.
1: It makes display “STOP” in
SV display.
0R/W
Input type
selection
XI 6 0 to 16 (See P. 18)Note 1R/W×
(1) Name: A name of identifier is written.
(2) Identifier: The code to identify the data is written.
(3) No. of digits: The number of maximum digits is written.
(4) Data range: The range of reading or writing data is written.
(5) Factory set value: The factory set value of data is written.
(6) Attribute: The data accessing direction is written.
RO: Read only (Data direction: Controller Host computer)
R/W: Read and Write (Data direction: Controller Host computer)
(7) CH: ×: Identifier with channel
: Identifier without channel
!"
!"!"
!"
Data sending during polling
Each time the host computer sends ACK (acknowledgement), the controller sends data corresponding
to the respective identifier in the order specified in a list of communication identifiers.
Communication is not possible when an identifier is specified that the controller can not
recognize.
Name Iden-
tifier
No. of
digits
Data range
STOP display
selection
DX 1 0: It makes display “STOP”
PV display.
1: It makes display “STOP”
SV display.
Input type
selection
XI 6 0 to 16 (See P. 18)
To be send in this order.