Specifications
2. DETAILS OF PARAMETER SETTING
IMR01H03-E4
26
2.7 F32 Alarm Output Function
"#
"#"#
"#
Alarm output logic selection (LGA)
Select the alarm output logic of alarm 1 (Normal equipment), alarm 2 (Option) and alarm 3 (Option).
The channel number displayed on the CH display unit corresponds to the relevant alarm. The setting
is made for each channel number. In addition, output logic of alarm 1 to alarm 3 can be
simultaneously set.
Conduct setting so as to meet the instrument specification.
An incorrect setting may cause a malfunction.
Channel
display
Alarm Details of setting Factory
set value
1ALM1
[Alarm 1]
0000: FAIL alarm
0001: Logical OR of alarm 1 in all channels (E
nergized
)
0002: Logical OR of alarm 2 in all channels (E
nergized
)
0003: Logical OR of alarm 3 in all channels (E
nergized
)
0004: Logical OR of alarm 1 and alarm 2 in all channels
(E
nergized
)
0005: Logical OR of alarm 1 and alarm 3 in all channels
(E
nergized
)
0006: Logical OR of alarm 2 and alarm 3 in all channels
(E
nergized
)
0007: Logical OR of alarm 1, alarm 2 and alarm 3 in all
channels (E
nergized
)
0008: Logical OR of alarm 1 in all channels (De-e
nergized
)
0009: Logical OR of alarm 2 in all channels (De-e
nergized
)
0010: Logical OR of alarm 3 in all channels (De-e
nergized
)
0011: Logical OR of alarm 1 and alarm 2 in all channels
(De-e
nergized
)
0012: Logical OR of alarm 1 and alarm 3 in all channels
(De-e
nergized
)
0013: Logical OR of alarm 2 and alarm 3 in all channels
(De-e
nergized
)
0014: Logical OR of alarm 1, alarm 2 and alarm 3 in all
channels (De-e
nergized
)
0001
2ALM2
[Alarm 2]
0000 to 0014: Same as ALM1 0002
3ALM3
[Alarm 3]
0000 to 0014: Same as ALM1 0003
Alarm output is only relay contact output.