Specifications

2. DETAILS OF PARAMETER SETTING
IMR01H03-E4
24
2.6 F31 Output Function
"#
"#"#
"#
MA900
(1) Control output logic selection 1 (LGo1)
This data is 0000 fixation. This data must not set the set value besides 0000.
Channel
display
Output
number
Details of setting Factory set
value
1OUT1
0000: Heat-side control output of CH1 0000
2OUT2
0000: Heat-side control output of CH2
3OUT3
0000: Heat-side control output of CH3
4OUT4
0000: Heat-side control output of CH4
(2) Control output logic selection 2 (LGo2)
Select the output logic of the output 2 (OUT5 to OUT8).
The channel number displayed on the CH display unit corresponds to the relevant output number.
The setting is made for each channel number. In addition, OUT5 to OUT8 can be simultaneously set.
Conduct setting so as to meet the instrument specification.
An incorrect setting may cause a malfunction.
Channel
display
Output
number
Details of setting Factory set
value
1OUT5
0000: No output
0001: Cool-side control output of CH1
1
0002: No output
0003: No output
0004: Alarm 3 of CH1
2
0005: Alarm 3 of CH2
2
0006: Alarm 3 of CH3
2
0007: Alarm 3 of CH4
2
0008 to 0011: No output
Factory set
value varies
depending on
the instrument
specification.
2OUT6
0000: No output
0001: Cool-side control output of CH2
1
0002 to 0007: Same as OUT5
0008 to 0011: No output
3OUT7
0000: No output
0001: Cool-side control output of CH3
1
0002 to 0007: Same as OUT5
0008 to 0011: No output
1
Setting becomes effective at the time of heat/cool control.
2
Not output when alarm 3 corresponds to the FAIL alarm.
Continued on the next page.