Specifications
2. DETAILS OF PARAMETER SETTING
IMR01H03-E4
22
2.5 F24 Contact Input Specification
Setting is common to all channels.
When the MA901 instrument specification corresponds to heater break alarm, the contact
input can't be added. Therefore, do not use this parameter.
"#
"#"#
"#
Contact input logic selection (diSL)
The contact input logic selection sets the set value about the following contents.
•
STOP selection
Selected whether to stop when the contact is opened or when the contact is closed.
•
Memory area selection
Memory area selection 1 to 8: These contents are selected when any of the memory areas from 1
to 8 is selected by the contact input.
Memory area selection 1 to 7: For example, when a digital switch starting from “0” is used,
select the memory area number when the memory area number
must match the digital switch number.
If the selection of the memory areas from 1 to 7 is chosen, no memory area 8 can be
selected by the contact input. In this case, select the memory area by the front key.
•
Used/unused of DI SET terminal (No. 43)
The method of establishment is set when the memory area is selected.
When the DI SET terminal (No. 43) is used:
Select the area 0.5 seconds after the DI SET terminal is closed.
When the DI SET terminal (No. 43) is not used:
Select the memory area 2 seconds after the area is selected.
Details of
setting
STOP selection Memory area
selection
Used/unused of
DI SET terminal
(No. 43)
Factory
set value
0000 When contact input
(RUN/STOP transfer)
opens, stop.
Memory area transfer
1 to 8
Used 0000
0001 When contact input
(RUN/STOP transfer)
opens, stop.
Memory area transfer
1 to 8
Unused
0002 When contact input
(RUN/STOP transfer)
opens, stop.
Memory area transfer
1 to 7
Used
Continued on the next page.