Specifications
2. DETAILS OF PARAMETER SETTING
IMR01H03-E4
19
(3) Decimal point position setting (PGdP)
Details of setting Factory set value
0000 No digit below decimal point (!!!!) Note 1
0001 1 digit below decimal point (!!!.!)
0002 2 digits below decimal point (!!.!!) *
0003 3 digits below decimal point (!.!!!) *
* When input type is thermocouple and RTD, no setting can be changed.
Note 1 Factory set value varies depending on the instrument specification.
See. 2.1 Attention Items in Setting (P. 12).
(4) Setting limiter [high limit] (SLH)
Setting limiter [low limit] (SLL)
Details of setting Factory set
value
K −199 to +1372 °C (−326 to +2502 °F) Factory set
−199.9 to +999.9 °C (−199.9 to +999.9 °F) value varies
J −199 to +1200 °C (−326 to +2192 °F) depending on
−199.9 to +999.9 °C (−199.9 to +999.9 °F) the instrument
R 0 to 1769 °C (0 to 3216 °F) specification.
S 0 to 1769 °C (0 to 3216 °F)
B 0 to 1820 °C (0 to 3308 °F)
E 0 to 1000 °C (0 to 1832 °F)
Thermocouple N 0 to 1300 °C (0 to 2372 °F)
0 to 999.9 °C (0 to 999.9 °F)
T −199 to +400 °C (−326 to +752 °F)
−199.9 to +400.0 °C (−199.9 to +752.0 °F)
W5Re/W26Re 0 to 2320 °C (0 to 4208 °F)
PL II 0 to 1390 °C (0 to 2534 °F)
U −199 to +600 °C (−326 to +1112 °F)
−199.9 to +600.0 °C (−199.9 to +999.9 °F)
L 0 to 900 °C (0 to 1652 °F)
RTD Pt100 (JIS/IEC
1
) −199.9 to +649.0 °C
JPt100 (JIS) (−199.9 to +999.9 °F)
0 to 5 V DC −1999 to +9999 SLH: 100.0
Voltage
2
1 to 5 V DC (programmable scale) SLL: 0.0
0 to 10 V DC
1
IEC (International Electrotechnical Commission) is equivalent to JIS, DIN and ANSI.
2
In case of voltage/current inputs, SLH can be set below SLL.
Set the setting limiter referring to the 4. INPUT RANGE TABLES (P. 55).
See. 2.1 Attention Items in Setting (P. 12).