Specifications

2. DETAILS OF PARAMETER SETTING
IMR01H03-E4
18
2.3 F21 Input Specification
The setting items (InP, UnIT, PGdP, SLH and SLL) in the function block F21 are set for each channel.
In addition, they can be set simultaneously for all channels.
(1) Input type selection (InP)
Details of setting Factory set value
0000 K Factory set value
0001 J varies depending on
0002 R the input type.
0003 S
0004 B
0005 E Thermocouple *
0006 N (TC)
0007 T
0008 W5Re/W26Re
0009 PL II
0010 U
0011 L
0012 Pt100 RTD *
0013 JPt100
0014 0 to 5 V DC Voltage *
0015 1 to 5 V DC
0016 0 to 10 V DC
* Input type cannot be changed because the hardware is different.
See 2.1 Attention Items in Setting (P. 12).
(2) Display unit selection (UnIT)
Details of setting Factory set value
0000 °C 0000
0001 °F
The invalidity in case of the voltage inputs.
See 2.1 Attention Items in Setting (P. 12).