Specifications

2. DETAILS OF PARAMETER SETTING
IMR01H03-E4
15
Continued from the previous page.
If the number of digits below the decimal point is changed in the decreasing direction, the decreased
number of digits is omitted.
Example: Suppose set SLH is 99.99, if change decimal point position from 0 to 2.
The figures below the decimal point are omitted,
and as a result SLH becomes 99.
In the above example, it the position of the decimal point is returned to 2 from 0, SLH
becomes 99.00.
Set SLL and SLH so that SLL may not be equal to SLH when the position of the decimal point is
changed. Otherwise malfunction may result.
Example: When the position of the decimal point is changed to 0 at SLL=999.1 and SLH=999.9
!"
!"!"
!"
When changed parameter of setting limiter [high limit/low limit]
When change setting limiter [high limit/low limit], all the set value of a list shown below is initialized.
Set it in value to use once again. However no change is made if the set value is within the range
changed.
Mode Description
Alarm 1 differential gap
Engineering mode Alarm 2 differential gap
Alarm 3 differential gap
ON/OFF action differential gap
Setup setting mode PV bias
Control loop break alarm deadband
Alarm 1
Alarm 2
Parameter setting mode Alarm 3
Heat-side proportional band
Overlap/deadband *
Setting change rate limiter
SV setting & CT monitor mode Set value (SV)
* In case of MA901, this item is not provided.
Example: For temperature input, voltage/current inputs
If the setting is made so that the span becomes narrower, there may be a case where the related set
value becomes smaller or 0.
(SLH) (SLH)
(SLL) (SLH) (SLL)