Specifications

2. DETAILS OF PARAMETER SETTING
IMR01H03-E4
13
Continued from the previous page.
Mode Description Default value
TC input RTD input Voltage input
Control loop break alarm 8.0 minutes
Control loop break alarm
deadband
0 °C [°F] 0.0 °C [°F] 0.0 %
Alarm 1 50 °C [°F] 50.0 °C [°F] 5.0 % of span
Alarm 2
Parameter Alarm 3
setting mode Heat-side proportional band 30 °C [°F] 30.0 °C [°F] 3.0 % of span
Integral time 240 seconds
Derivative time 60 seconds
Anti-reset windup 100 %
Cool-side proportional band * 100 % of heat-side proportional band
Overlap/deadband * 0 °C [°F] 0.0 °C [°F] 0.0 %
Setting changing rate limiter OFF
SV setting &
CT monitor
mode
Set value (SV) 0 °C [°F] 0.0 °C [°F] 0.0 %
* In case of MA901, these items are not provided.