Specifications

2. DETAILS OF PARAMETER SETTING
IMR01H03-E4
12
2.1 Attention Items in Setting
If any of the following parameter is changed, the relevant set value is initialized or is automatically
converted.
Before changing the set values, always record all of them (SV setting & CT monitor mode,
setup setting mode, parameter setting mode and engineering mode).
After changing the set values, always check all of them (SV setting & CT monitor mode,
setup setting mode, parameter setting mode and engineering mode).
!"
!"!"
!"
When changed parameter of input type selection or engineering unit setting
When change a input type and unit, all the set value of a list shown below is initialized. Set it in value
to use once again.
Mode Description Default value
TC input RTD input Voltage input
Decimal point position 0
1
1
2
Setting limiter [high limit] Maximum settable value 100.0 %
Setting limiter [low limit] 0.0 %
Alarm 1 hold action
0 (Without alarm hold action)
Alarm 1 differential gap 2 °C [°F] 2.0 °C [°F] 0.2 % of span
Alarm 1 action at input error 0 (Without action at input error)
Engineering Alarm 2 hold action 0 (Without alarm hold action)
mode Alarm 2 differential gap 2 °C [°F] 2.0 °C [°F] 0.2 % of span
Alarm 2 action at input error 0 (Without action at input error)
Alarm 3 hold action 0 (Without alarm hold action)
Alarm 3 differential gap 2 °C [°F] 2.0 °C [°F] 0.2 % of span
Alarm 3 action at input error 0 (Without action at input error)
ON/OFF action differential gap 2 °C [°F] 2.0 °C [°F] 0.2 % of span
Heater break alarm 1 OFF
Setup setting Heater break alarm 2
3
OFF
mode PV bias 0 °C [°F] 0.0 °C [°F] 0.0 %
Digital filter OFF
1
0: No digit below decimal point
2
1: 1 digit below decimal point
3
In case of MA901, this item is not provided.
Continued on the next page.