6. MODBUS COMMUNICATION PROTOCOL
IMR01H02-E3
74
Continued from the previous page.
Address CH Name
1401H (5121) CH1
1402H (5122) CH2
1403H (5123) CH3
1404H (5124) CH4 Used/unused of
1405H (5125) CH5 channels
1406H (5126) CH6
1407H (5127) CH7
1408H (5128) CH8
1409H (5129)
143CH (5180)
Unused
143DH (5181) CH1
143EH (5182) CH2
143FH (5183) CH3
1440H (5184) CH4 Alarm 1
1441H (5185) CH5
1442H (5186) CH6
1443H (5187) CH7
1444H (5188) CH8
1445H (5189)
1450H (5200)
Unused
1451H (5201) CH1
1452H (5202) CH2
1453H (5203) CH3
1454H (5204) CH4 Control loop break
1455H (5205) CH5 alarm deadband (LBD)
1456H (5206) CH6
1457H (5207) CH7
1458H (5208) CH8
1459H (5209)
1464H (5220)
Unused
Address CH Name
1465H (5221) CH1
1466H (5222) CH2
1467H (5223) CH3
1468H (5224) CH4 Alarm 2
1469H (5225) CH5
146AH (5226) CH6
146BH (5227) CH7
146CH (5228) CH8
146DH (5229)
148CH (5260)
Unused
148DH (5261) CH1
148EH (5262) CH2
148FH (5263) CH3
1490H (5264) CH4 Alarm 3
1491H (5265) CH5
1492H (5266) CH6
1493H (5267) CH7
1494H (5268) CH8
1495H (5269)
14A0H (5280)
Unused
The accessible data (holding register) address range is from 0000H to 02EEH and 1388H to
14A0H. Addresses in which data (holding register) is accessible are from 0000H to 02EEH
and from 1388H to 14A0H. If any address other than 0000H to 02EEH and 1388H to
14A0H is accessed, an error response message (error code: 2) returns.
However, no error returns for any address from 03E8H to 0563H. Therefore, do not access
any of the above addresses.