Instruction manual

6. MODBUS COMMUNICATION PROTOCOL
IMR01H02-E3
67
(4) Read/Write data
(Data corresponding to memory area)
Address CH Name
1388H (5000)
Memory area number
selection
1389H (5001) CH1
138AH (5002) CH2 Set value (SV)
138BH (5003) CH3
138CH (5004) CH4
138DH (5005)
139CH (5020)
Unused
139DH (5021) CH1 Proportional band
139EH (5022) CH2
139FH (5023) CH3
For heat/cool control:
13A0H (5024) CH4
Heat-side proportional band
13A1H (5025)
13B0H (5040)
Unused
13B1H (5041) CH1
13B2H (5042) CH2 Integral time
13B3H (5043) CH3
13B4H (5044) CH4
13B5H (5045)
13C4H (5060)
Unused
13C5H (5061) CH1
13C6H (5062) CH2 Derivative time
13C7H (5063) CH3
13C8H (5064) CH4
13C9H (5065)
13D8H (5080)
Unused
13D9H (5081) CH1
13DAH (5082) CH2 Anti-reset windup
13DBH (5083) CH3
13DCH (5084) CH4
13DDH (5085)
13ECH (5100)
Unused
13EDH (5101) CH1
13EEH (5102) CH2 Setting change rate
13EFH (5103) CH3 limiter
13F0H (5104) CH4
Address CH Name
13F1H (5105)
1400H (5120)
Unused
1401H (5121) CH1
1402H (5122) CH2 Used/unused of
1403H (5123) CH3 channels
1404H (5124) CH4
1405H (5125)
1414H (5140)
Unused
1415H (5141) CH1
1416H (5142) CH2 Cool-side
1417H (5143) CH3 proportional band
1418H (5144) CH4
1419H (5145)
1428H (5160)
Unused
1429H (5161) CH1
142AH (5162) CH2 Overlap/deadband
142BH (5163) CH3
142CH (5164) CH4
142DH (5165)
143CH (5180)
Unused
143DH (5181) CH1
143EH (5182) CH2 Alarm 1
143FH (5183) CH3
1440H (5184) CH4
1441H (5185)
1450H (5200)
Unused
1451H (5201) CH1
1452H (5202) CH2 Control loop break
1453H (5203) CH3 alarm deadband (LBD)
1454H (5204) CH4
1455H (5205)
1464H (5220)
Unused
Continued on the next page.