Instruction manual
6. MODBUS COMMUNICATION PROTOCOL
IMR01H02-E3
57
Continued form the previous page.
Name Data range Factory set
value
Attri-
bute
EEPROM storage
status
1
0: The content of the EEPROM does not
coincide with that of the memory.
1: The content of the EEPROM coincides
with that of the memory.
----- RO
Set value monitor Within input range. ----- RO
Set value (SV) ! Within input range. 0 or 0.0 R/W
PID/AT selection 0: PID control 1: Autotuning (AT) 0 R/W
Proportional band
2
!
0 (0.0) to span
However, 9999 digits or less
(0 or 0.0: ON/OFF action)
Temperature input:
30 or 30.0
Voltage input: 3.0
R/W
Cool-side
proportional band !
(This item does not use
in the MA901.)
1 to 1000 % of heat-side proportional band 100 R/W
3
Integral time ! 0 to 3600 seconds (0: PD action) 240 R/W
Derivative time ! 0 to 3600 seconds (0: PI action) 60 R/W
Overlap/deadband !
(This item does not use
in the MA901.)
-span to +span
4
(Within -1999 to +9999 digits)
Temperature input:
0 or 0.0
Voltage input: 0.0
R/W
3
Anti-reset windup ! 0 to 100 % of heat-side proportional band
(0: Integral action OFF)
100 R/W
1
The contents of the buffer memory and those of the EEPROM can be checked.
When data is 0: The contents of the buffer memory do not match with those of the EEPROM.
• As data is being written to the EEPROM in backup mode, do not turn the power
off. If turned off, no set values are stored.
• If the set value is changed after the backup mode is changed to the buffer mode,
0 is set (mismatch). As the set value changed is not backup, select the backup
mode if necessary.
When data is 1: The contents of the buffer memory match with those of the EEPROM.
(Data write to the EEPROM is completed.)
2
For heat/cool control: Heat-side proportional band
3
In case of heat control, become RO (read only).
4
Minus (-) setting results in overlap.
Continued on the next page.