Instruction manual

6. MODBUS COMMUNICATION PROTOCOL
IMR01H02-E3
57
Continued form the previous page.
Name Data range Factory set
value
Attri-
bute
EEPROM storage
status
1
0: The content of the EEPROM does not
coincide with that of the memory.
1: The content of the EEPROM coincides
with that of the memory.
----- RO
Set value monitor Within input range. ----- RO
Set value (SV) ! Within input range. 0 or 0.0 R/W
PID/AT selection 0: PID control 1: Autotuning (AT) 0 R/W
Proportional band
2
!
0 (0.0) to span
However, 9999 digits or less
(0 or 0.0: ON/OFF action)
Temperature input:
30 or 30.0
Voltage input: 3.0
R/W
Cool-side
proportional band !
(This item does not use
in the MA901.)
1 to 1000 % of heat-side proportional band 100 R/W
3
Integral time ! 0 to 3600 seconds (0: PD action) 240 R/W
Derivative time ! 0 to 3600 seconds (0: PI action) 60 R/W
Overlap/deadband !
(This item does not use
in the MA901.)
-span to +span
4
(Within -1999 to +9999 digits)
Temperature input:
0 or 0.0
Voltage input: 0.0
R/W
3
Anti-reset windup ! 0 to 100 % of heat-side proportional band
(0: Integral action OFF)
100 R/W
1
The contents of the buffer memory and those of the EEPROM can be checked.
When data is 0: The contents of the buffer memory do not match with those of the EEPROM.
As data is being written to the EEPROM in backup mode, do not turn the power
off. If turned off, no set values are stored.
If the set value is changed after the backup mode is changed to the buffer mode,
0 is set (mismatch). As the set value changed is not backup, select the backup
mode if necessary.
When data is 1: The contents of the buffer memory match with those of the EEPROM.
(Data write to the EEPROM is completed.)
2
For heat/cool control: Heat-side proportional band
3
In case of heat control, become RO (read only).
4
Minus (-) setting results in overlap.
Continued on the next page.