5. RKC COMMUNICATION PROTOCOL
IMR01H02-E3
39
Continued from the previous page.
Name Iden-
tifier
No. of
digits
Data range Factory set
value
Attri-
bute
CH
Alarm 3 !
A3
6 Process alarm, SV alarm
1
:
Same as input range
Deviation alarm
1
:
-span to + span
(Within -1999 to +9999 digits)
Temperature
input:
50 or 50.0
Voltage input:
5.0
R/W
2
×
Proportional
band
3
!
P1
6 0 (0.0) to span
However, 9999 digits or less
(0 or 0.0: ON/OFF action)
Temperature
input:
30 or 30.0
Voltage input:
3.0
R/W
×
Cool-side
proportional
band !
(This item does not
use in the MA901)
P2
6 1 to 1000 % of heat-side
proportional band
100 R/W
4
×
Integral time !
I1
6 0 to 3600 seconds
(0: PD action)
240 R/W
×
Derivative time !
D1
6 0 to 3600 seconds (0: PI action) 60 R/W
×
Anti-reset windup
!
W1
6 0 to 100 % of heat-side
proportional band
(0: Integral action OFF)
100 R/W
×
Overlap/
deadband !
(This item does not
use in the MA901)
V1
6 -span to +span
5
(Within -1999 to +9999 digits)
Temperature
input: 0 or 0.0
Voltage input:
0.0
R/W
4
×
1
Process alarm = Process high alarm, Process low alarm, Process high alarm (with hold action),
Process high alarm (with hold action)
SV alarm = SV high alarm, SV low alarm
Deviation alarm = Deviation high alarm, Deviation low alarm, Deviation high/low alarm, Band
alarm, Deviation high alarm (with hold action), Deviation low alarm (with hold
action), Deviation high/low alarm (with hold action)
2
When there is not alarm 3, attribute becomes RO (read only).
When the alarm 3 is FAIL alarm, attributes become RO (read only).
3
For heat/cool control: Heat-side proportional band
4
In case of heat control, become RO (read only).
5
Minus (-) setting results in overlap.
Continued on the next page.