Instruction manual

5. RKC COMMUNICATION PROTOCOL
IMR01H02-E3
35
!"
!"!"
!"
Communication identifier list
Name Iden-
tifier
No. of
digits
Data range Factory set
value
Attri-
bute
CH
Model code
ID
32 Display the model code ----- RO
Measured value
(PV)
M1
6 Within input range. ----- RO
×
Current
transformer 1
input value
M2
6 CTL6P: 0.0 to 30.0 A
CTL12: 0.0 to 100.0 A
----- RO
×
Current
transformer 2
input value
(This item does not
use in the MA901)
M3
Set value monitor
MS
6 Within input range. ----- RO
×
Burnout
B1
1 0: OFF 1: ON ----- RO
×
Alarm 1 status
AA
1 0: OFF 1: ON ----- RO
×
Alarm 2 status
AB
Alarm 3 status
AC
Continued on the next page.