3. DESCRIPTION OF EACH MODULES
IMSRM15-E6
85
Zooming function
Can be set from 0 to 100 for each of the high and low sides of the relevant output data.
(High
Low)
[Example]
When a temperature of 100 to 200
C at measured
value (PV) 1 is necessary to recorded for the
temperature range from 0 to 400
C.
Set the relevant values as follows.
AO function selection = Temperature measured value
Setting of channel corresponding to AO = 1 CH
AO zoom high = 50 %
AO zoom low = 25 %
In this case, a percentage of 0 to 100 % is output
between 100 and 200
C.
The setting of the zoom function becomes valid in recorder output mode.
AO display scaling function
Any analog output from the H-AO module can match 1 to 5 V or 4 to 20 mA on the display.
[Example]
A screen display of 0 to 400
C is required by
using the H-AO module with an output of 4 to 20
mA. Set the relevant values as follows.
AO display scale high: 400
AO display scale low: 0
Thus, a temperature of 0
C is displayed at an
output of 4 mA, and a temperature of 400
C, at an
output of 20 mA.
The setting of the AO display scaling function becomes valid in manual mode.
Current
output
Display
20 mA
4 mA
400
C
0
C
20 m
A
Current output
PV (
C)
0 100 200 300 400
4 m
A