Instruction manual
3. DESCRIPTION OF EACH MODULES
IMSRM15-E6
79
Data comparison output function
This function is used to output the result of comparison between the measured value and measured
value (or set value and set value) within the same group.
Event DO function selection
Event DO
corresponding
channel setting
Event DO mode
select setting
Data 1 Data 2
Temperature input measured value (PV)
comparison
Comparison between PV and PV
1 to 20 CH
(H-TIO/H-CIO module)
1 to 20 CH
(H-TIO/H-CIO module)
Temperature set value (SV) comparison
Comparison between SV and SV
1 to 20 CH
(H-TIO/H-CIO module)
1 to 20 CH
(H-TIO/H-CIO module)
AI input measured value (PV) comparison
Comparison between PV and PV
1 to 40 CH
(H-AI module)
1 to 40 CH
(H-AI module)
TI input measured value (PV) comparison
Comparison between PV and PV
1 to 40 CH
(H-TI module)
1 to 40 CH
(H-TI module)
[Relationship between output and comparison]
Computing equation: The output turns ON at (Data 2)
(Data 1) 0
This means:
The output turns ON if (Data 2) is smaller than or equal to (Data 1). {Data 2
Data 1}
The output turns OFF if (Data 2) is larger than (Data 1). {Data 2
Data 1}
The differential gap during comparison can be set. (All channel common setting)
Setting range: 0.00 to 10.00
of input range
Each event output can be assigned from the dedicated host computer via communication.
For details on event output selection, refer to SR Mini/SR Mini HG SYSTEM Supplementary
Information Initialize Settings [Extended Communications] (IMSRM07-E
).