Instruction manual
3. DESCRIPTION OF EACH MODULES
IMSRM15-E6
73
Open collector output (H-DO-A and H-DO-C type)
The output status is an 8 points/common open collector output.
For the internal circuit driver of the H-DO module, connect the minus (
) terminal of an external
power supply (24 V DC) to the number 6 terminal and connect the positive (+) terminal of the power
supply to the common line of each output.
In using the open collector output, an external power supply of 24 V DC is required.
Note that if this power supply is not connected, there will be no output from the
module.
Open collector output wiring example
External power supply (24 V DC)
Load voltage: 12 to 24 V DC
Maximum load current:
0.1 A/point
0.8 A/common
1
2
3
4
5
6
7
8
9
10
COM
DO1
DO2
DO3
DO4
24 V DC
DO5
DO6
DO7
DO8
+
12 to 24 V DC
-
+
10
COM (+)
COM (-)
DO1
DO8
Load
6
2
1
Load