Instruction manual
3. DESCRIPTION OF EACH MODULES
IMSRM15-E6
72
3.9.3 Functional description
(1) Alarm output function (only for H-DO-A, H-DO-B and H-DO-D types)
Alarm output function types
Any alarm selected from the following alarm output functions can be output for each channel.
Temperature alarm output (alarm 1 and alarm 2)
This alarm is output when the measured value (PV) of the H-TIO module is within the alarm setting
range.
The alarm 1 and alarm 2 are output for each channel.
Heater break alarm output
This alarm is output for each channel when the heater current detected by the current transformer is
within the heater break alarm setting range.
Burnout alarm output
This alarm is output for each channel when the input (sensor) breaks or the input value exceeds the
scaling range.
Loop break alarm output
This alarm is output for each channel when an error occurs in the control loop.
AI alarm output (AI alarm 1 and AI alarm 2)
This alarm is output when the measured value (PV) of the H-AI module is within the AI alarm setting
range. The AI alarm 1 and AI alarm 2 are output for each channel.
Output type
Relay contact output (H-DO-A and H-DO-B type)
H-DO-A type
Output status: 1 a contact output
4 points/common
NO
COM
NO
NO
NO
Rating: 250 V AC, 24 V DC
Maximum load current:
1 A/point (Resistive load)
4 A/common (Resistive load)
H-DO-B type
All point independent common output
1
2
3
4
6
7
8
9
NO
NO
NO
NO
DO1
DO2
DO3
DO4
Rating: 250 V AC, 24 V DC
Maximum load current:
1 A/point (Resistive load)