3. DESCRIPTION OF EACH MODULES
IMSRM15-E6
68
3.8.3 Functional description
(1) Digital input function (H-DI-A)
This is a function to switch the operation status of the control unit (refer to below) using the external
signal fed into the H-DI-A module which is connected to the control unit. The operation status can be
switched over by the open/close state of the digital input terminals 1 to 8 of the H-DI-A module.
Operation state types: Memory area selection, Control RUN/STOP selection and Alarm interlock release
For memory area selection, configure an external contact circuit or use a contact output signal from the
PLC, if necessary.
After the contact is closed, it takes a short time until the action of this device is actually selected.
Therefore, pay attention to this delay time if the device is used together with a PLC, etc.
Connect external power (24 V DC) to the number 1 and number 6 COM (common) terminals
on the H-DI module so that these terminal sides become positive (+).
Control area
Terminal No.
1 2 3 4 5 6 7 8
1 - 2
1 - 3
1 - 4
: Open : Closed
The memory area (control area) is established by closing terminal number 5
(ENABLE terminal). [Function mode 1*]
* The function mode types below can be selected for the digital input function of the H-DI-A
module. The digital inputs (DI) function can be set following function mode 1 to 2 in
operation panel or host communication (initialize settings [extended communications]).
Function mode 1 (factory set value)
Memory area selection (ENABLE terminal is used)
After area selection setting, the actual area is changed by detecting the ENABLE edge.
Control RUN/STOP selection
Alarm interlock release
Function mode 2
Memory area selection
The actual area is changed approximately 2 seconds after area selection setting.
Control RUN/STOP selection
Alarm interlock release
Alarm interlock release (contact closed: alarm interlock release)
(No alarm interlock function is activated if the contact is in the normally closed
state.)
Control RUN/STOP selection (contact closed: RUN, contact open: STOP)