Instruction manual
3. DESCRIPTION OF EACH MODULES
IMSRM15-E6
62
Voltage pulse output
This output is for driving the SSRs and 12 V DC is output during the outputting.
Current and voltage output
The current output can be selected from 4 to 20 mA DC or 0 to 20 mA DC, and the voltage output can
be selected from 0 to 1 V DC, 0 to 5 V DC, 0 to 10 V DC or 1 to 5 V DC. (Specify when ordering)
It is possible only in the 1 to 5 V DC voltage output to make a common connection of the
minus terminals of the outputs, including the voltage pulse output. (Refer to P. 99.)
Triac output
This output can directly drive AC power by the small SSR built in the module. The zero-cross control
method is employed.
Open collector output
This transistor sink output uses switching between the transistor emitter and collector. An external
power supply of 12 to 24 V DC is connected to the load in series.
Open collector output wiring example
The minus ( ) terminals of open collector outputs, OUT1 and OUT2 are connected within
the module.
+
Allowable load resistance: 600 or more
+
Allowable load resistance: 500 or less (Current output)
1 k
or more (Voltage output)
12 to 24 V DC
OUT2
OUT1
+
+
+
-
-
-
H-CIO-A type
Load
Load
Maximum load current: 100 mA or less
+
Capacity: 0.5 A (At an ambient temperature of 40 C)
Maximum load voltage: 250 V AC
SSR