Instruction manual
3. DESCRIPTION OF EACH MODULES
IMSRM15-E6
61
(2) Output function
Channel number
In the same way as the input terminals, for the H-CIO module, CH1 and CH2 are assigned to the
output terminals of the H-CIO module in order from the top.
If several H-CIO modules are mounted together, channel numbers are assigned automatically to these
modules in order from the left. (Number of connection: Up to 5 modules/control unit)
Channel number assignment
The control output from the output terminals differs depending on the slave channel control
action type.
Slave channel control action type
H-CIO-A-F or H-CIO-A-D type H-CIO-A-B or H-CIO-A-W type
OUT1 Master channel manipulated output Slave channel heat-side control output
OUT2 Slave channel control output Slave channel cool-side control output
Output type
The desired output type can be selected from relay contact, voltage pulse, voltage, current, triac and
open-collector outputs for each of OUT1 and OUT2. (Specify when ordering.)
For the module of 1 module/2 channels, various output types cannot be mixed in the
module. One output type can be selected for each module.
For details on each output, refer to 8. SPECIFICATION (P. 128).
Relay contact output
Output status: Independent 1a contact output (closed during outputting)
NO
Rating: 250 V AC, 3 A (Resistive load)
H-CIO-A H-CIO-A
CH2 (OUT2)
Slave-side control
output or cool-side
control output
CH1 (OUT1)
Master-side
manipulated output or
heat-side control output
CH1
H-CIO-A
CH2
CH3
CH4