3. DESCRIPTION OF EACH MODULES
IMSRM15-E6
55
(6) Heater break alarm function (Optional)
The heater break alarm function is used to detect the current flowing into the load (heater) by using the
current transformer (CT), thereby producing a heater break alarm when a heater break occurs.
(Refer to P. 123.)
This function can be added only to the H-TIO-A, C or D type module.(1 point/control loop)
For H-TIO-A/C/D module with voltage/current output, no heater break alarm function can be
used.
The heater break alarm can be output as summary output (OR output) from the digital output
block in the H-PCP-A/B module. For details, refer to 3.3 H-PCP Module (P. 36).
The heater break alarm can be output independently for each channel by connecting the
H-DO-A/B/D module. For details, refer to 3.9 H-DO Module (P. 70).
(7) Control function
As standard, the H-TIO module employs the brilliant PID control method which can prevent overshoot
or disturbance (excluding the H-TIO-K module). (Refer to P. 113.)
The selectable control action type differs depending on the H-TIO module type. (Refer to the table
below.)
Type ON/OFF action
PID action with
autotuning
Heat/Cool PID action
with autotuning
PID action with
autotuning
(With fuzzy control)
Position
proportioning
control action
H-TIO-A
H-TIO-B
H-TIO-C
H-TIO-D
H-TIO-E
H-TIO-F
H-TIO-G
H-TIO-H
H-TIO-J
H-TIO-K
H-TIO-P
H-TIO-R
: Selectable : Not selectable