Instruction manual

3. DESCRIPTION OF EACH MODULES
IMSRM15-E6
41
Communication function
The H-PCP module has communication port COM.PORT1/COM.PORT2 and can be connected with
operation panel, host computer and extension control unit.
Interface: RS-422A or RS-232C
Protocol: RKC communication protocol
Ladder communication (Non-protocol type) [Z-190 specification]
Communication speed: 2400 bps, 4800 bps, 9600 bps and 19200 bps
(Select the communication speed by the dip switch in the H-PCP module)
Connection instrument: Operation panel, host computer, extension control unit, PLC
[Z-190 specification]
For the H-PCP-A/B module with the ladder communication, special specification code
“Z-190” must be specified at the end of the model code.
The H-TIO-K, H-CIO-A, H-DI-B and H-DO-C module cannot be used to the H-PCP-A/B
module with the specification of ladder.
For details on the dip switch settings, refer to 3.3.4 Settings before operation (P. 42).