Instruction manual
2. SYSTEM CONFIGURATION
IMSRM15-E6
26
Continued from the previous page.
[Example] When power supply voltage of 12V
When using H-TIO-B modules together with H-TIO-D modules
As the H-TIO-D module consumes an output current of 80 mA/slot and the H-TIO-B module, an
output current of 40 mA, the following current is obtained.
For H-TIO-D (3 modules): 80 mA
3 = 240 mA,
For H-TIO-B (4 modules): 40 mA
4 = 160 mA
240 mA + 160 mA = 400 mA
1000 mA: Maximum power supply capacity
The above current does not exceed the maximum power supply capacity (1000 mA). However, as one
H-TIO-D module is assumed to correspond to two function modules, up to 7 function modules can
be mounted.
When using H-DO-A-M modules together with H-TIO-B modules
As an example in which the H-DO modules need to be added for outputting the alarm independently
for each channel, when (H-DO-A-M modules: 3 modules) are added to (H-TIO-B modules: 7
modules):
Each consuming output current becomes as follows.
For H-TIO-B modules (7 modules): 40 mA
7 = 280 mA,
For H-DO-A-M modules (3 modules): 140 mA
3 = 420 mA
280 mA + 420 mA = 700 mA
1000 mA: Maximum power supply capacity
As the total current described above does not exceed the maximum power supply capacity (1000 mA),
up to 10 function modules can be mounted.
H-TIO-D
80 mA
H-TIO-D
80 mA
H-TIO-D
80 mA
H-TIO-B (4 modules)
160 mA
H-DO-A-M
(3 modules)
H-TIO-B
(7 modules)