Instruction manual
1. OUTLINE
IMSRM15-E6
15
RTD input (H-TIO-A/B/C/D/E/F/G/K/P/R, H-TI-A/B, H-CIO-A)
Input type
Code
Input Range
0.0 to 400.0 C P 16
0 to 400 C P 17
-200 to +200 C P 18
-200.0 to +200.0 C P 21
JPt100
-50.00 to +150.00 C
1
P 22
-300 to +900 F P B4
0 to 800 F P B3
0.0 to 800.0 F P B7
-300.0 to +900.0 F
2
P B8
0.0 to 400.0 C D 16
0 to 400 C D 17
-200 to +200 C D 18
-200.0 to +200.0 C D 21
Pt100
-50.00 to +150.00 C
1
D 22
-300 to +1200 F D B5
0 to 800 F D B4
0.0 to 800.0 F D B7
-300.0 to +1200.0 F
2
D B8
Voltage input and Current input (H-TIO-H/J, H-CIO-A)
Input type
Code
Input Range
0 to 10 mV DC 0.0 to 100.0 % 1 01
-10 to +10 mV DC 0.0 to 100.0 % G 01
0 to 100 mV DC 0.0 to 100.0 % 2 01
-100 to +100 mV DC 0.0 to 100.0 % U 01
Voltage
input
*
0 to 1 V DC 0.0 to 100.0 % 3 01
-1 to +1 V DC 0.0 to 100.0 % W 01
0 to 5 V DC 0.0 to 100.0 % 4 01
1 to 5 V DC 0.0 to 100.0 % 6 01
-5 to +5 V DC 0.0 to 100.0 % D 01
0 to 10 V DC 0.0 to 100.0 % 5 01
-10 to +10 V DC 0.0 to 100.0 % V 01
Current
input
*
0 to 20 mA DC 0.0 to 100.0 % 7 01
4 to 20 mA DC 0.0 to 100.0 % 8 01
* Display scale of the voltage and
current input can be changed.
1
The range with the resolution of 1/100 can be
specified only by H-TIO-E module.
2
The range can be specified only by H-TIO-F
module (high accuracy type).