1. OUTLINE
IMSRM15-E6
14
Input range table
Thermocouple input
Input type
Code
Input Range
0 to 400 C K 02
0 to 800 C K 04
0 to 1300 C K 11
0.0 to 400.0 C K 09
0.0 to 800.0 C K 10
K
0.0 to 1300.0 C
1
K 23
0 to 800 F K A1
0.0 to 800.0 F K A4
0 to 2400 F K A5
0.0 to 2400.0 F
1
K B4
-200.0 to +300.0 C
1
K 32
-100.0 to +400.0 C
2
K 36
0 to 400 C J 02
0 to 800 C J 04
0 to 1200 C J 06
0.0 to 400.0 C J 08
0.0 to 800.0 C J 09
J
0.0 to 1200.0 C
1
J 16
0 to 1600 F J A2
0.0 to 700.0 F J A4
0 to 2100 F J A5
0.0 to 1600.0 F
1
J B2
-200.0 to +300.0 C
1
J 26
0 to 1700 C R 03
R
0.0 to 1700.0 C
1
R 05
0 to 3000 F R A3
0 to 1700 C S 03
S
0.0 to 1700.0 C
1
S 04
0 to 3000 F S A3
0 to 1800 C B 03
B
3
0.0 to 1800.0 C
1
B 04
0 to 3000 F B A5
0 to 1000 C E 02
0.0 to 700.0 C E 03
0 to 400 C E 04
E
0.0 to 400.0 C
1
E 07
0.0 to 1000.0 C
1
E 08
0 to 1800 F E A3
0.0 to 1800.0 F
1
E A6
Input type
Code
Input Range
0.0 to 400.0 C T 06
0 to 400 C T 08
0 to 200 C T 09
-200 to +200 C T 10
T
0.0 to 200.0 C
1
T 12
-200.0 to +200.0 C
1
T 13
0.0 to 700.0 F T A7
0 to 700 F T A9
-300 to +400 F T B1
-300.0 to +400.0 F
1
T B3
0 to 1300 C N 02
N
0.0 to 1300.0 C
1
N 05
0 to 2300 F N A1
0.0 to 2300.0 F
1
N A4
0 to 1200 C A 03
PL II
0.0 to 1200.0 C
1
A 04
0 to 2300 F A A3
0.0 to 2300.0 F
1
A A5
W5Re/
W26Re
0 to 2300 C W 03
0.0 to 2300.0 C
1
W 04
0 to 3000 F W A3
0.0 to 600.0 C U 04
0 to 400 C U 05
-200 to +200 C U 06
0.0 to 400.0 C
1
U 03
U
-200.0 to +200.0 C
1
U 09
0 to 700 F U A5
-300 to +400 F U A6
0.0 to 700.0 F
1
U A8
-300.0 to +400.0 F
1
U A9
0 to 400 C L 01
0.0 to 400.0 C L 03
0.0 to 900.0 C L 04
L
0 to 900 C L 05
0 to 800 F L A1
0 to 1600 F L A2
0.0 to 800.0 F
1
L A5
0.0 to 1600.0 F
1
L A6
1
The range can be specified only by H-TIO-E/G/R, H-TI-B or H-CIO-A module (high accuracy type).
2
The range can be specified only by H-TIO-A/B/C/D [Z-1013 specification] or H-TI-C module [Z-1013
specification].
3
Accuracy is not guaranteed between 0 to 399 C (0 to 799 F) for type B thermocouple input.
(H-TIO-A/B/C/D/E/G/K/P/R, H-TI-B/C, H-CIO-A)