Instruction manual

8. SPECIFICATIONS
IMSRM15-E6
170
8.9 H-AO Module
Output
Number of inputs: H-AO-A: 4 points
(Isolated between output and CPU. Not isolated between each channel.)
H-AO-B: 2 points
(Isolated between each channel and between output and CPU.)
Output type: Voltage output: 0 to 10 mV DC, 0 to 100 mV DC, 0 to 1 V DC,
0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC
Current output: 0 to 20 mA DC, 4 to 20 mA DC
Specify when ordering
Resolution: 12 bits or more
Output impedance: Voltage output: Approx. 10
(0 to 10 mV DC, 0 to 100 mV DC)
0.1
or less (0 to 1 V DC, 0 to 5 V DC, 1 to 5 V DC,
0 to 10 V DC)
Current output: 5 M
or more
Allowable load resistance: Voltage output: 20 k
or more (0 to 10 mV DC, 0 to 100 mV DC)
1 k
or more (0 to 1 V DC, 0 to 5 V DC, 1 to 5 V DC,
0 to 10 V DC)
Current output: 500
or less
Setting method: Set via serial communication from the H-PCP module, or set from the
dedicated operation panel.
Selection of AO function: Manual mode
Recorder mode: Temperature measured value (PV)
Temperature set value (SV)
Temperature deviation value
Heat-side manipulated output value
Cool-side manipulated output value
H-AI module input value
H-TI module input value
H-TIO-K module feedback resistance input
Calibration function: Correction of zero and full scale points
Recorder mode
Type/channel selection: Type to be freely output and channel can be selected by AO function/
channel selection.
Output zooming function: Measured value data to be output is expanded and then output to AO.
Output change cycle: 200 ms