Instruction manual

8. SPECIFICATIONS
IMSRM15-E6
165
8.7.3 Event digital output module (H-DO-C)
Output
Output type: Open collector output
Number of outputs: 8 points
Number of common points: 1 point (8 points/common)
Isolation method: Photocoupler isolation
Open collector output: Load voltage: 12 to 24 V DC
Maximum load current: 0.1 A/point
0.8 A/common
Setting method: Set by H-PCP module via serial communication.
Alarm output types: Temperature alarm 1 status
Temperature alarm 2 status
Temperature burnout alarm status
Heater break alarm status
AI alarm 1 status
AI alarm 2 status
Loop break alarm status
PID/AT status
TI alarm 1 status
TI alarm 2 status
TI burnout alarm status
Event DI logic output status
Temperature deviation alarm
Temperature process alarm
Temperature set value alarm
AI process alarm
TI process alarm
Temperature process value comparison
Temperature set value comparison
AI process value comparison
TI process value comparison
Output function
Status output functions: Output on/off data such as temperature alarm 1 status, etc. owned by the
H-PCP module.
Channel numbers of H-TIO modules, etc. can be selected.
Status output
Alarm output
Comparison output