Instruction manual
8. SPECIFICATIONS
IMSRM15-E6
164
8.7.2 Digital output module (H-DO-D)
Output
Output type: Open collector output
Number of outputs: 16 points
Number of common points: Vcc: 2 points (8 points/common)
GND: 2 points (8 points/common)
Isolation method: Photocoupler isolation
Open collector output: Load voltage: 12 to 24 V DC
Maximum load current: 0.05 A/point
0.4 A/common
Setting method: Set by H-PCP module via serial communication.
The alarm type is set for each block consisting of eight channels.
Alarm output type: Temperature alarm 1
Temperature alarm 2
Burnout alarm
Heater break alarm
Loop break alarm
AI alarm 1
AI alarm 2
Unused
Self-diagnostic
Check item: RAM check
Watchdog timer
Operation at error occurrence in self-diagnosis:
FAIL lamp lights
Reset state
General specifications
Dimensions: 24 (W) 96 (H) 100 (D) mm
Weight: 140 g