Instruction manual
8. SPECIFICATIONS
IMSRM15-E6
158
8.5 H-CT Module
Input
Input type: Current transformer input (CT)
Number of inputs: 6 points
Number of common points: 3 points
(1-2 channel/common, 3-4 channel/common, 5-6 channel/common)
Isolation method: Photocoupler isolation
Input current: 0 to 30 A: CTL-6-P-N
0 to 100 A: CTL-12-S56-10L-N
Specify when ordering (Current transformer is sold separately)
Accuracy of heater current measurement:
5 % of input value or
2 A (The value whichever is greater)
Heater break alarm function
Setting range: 0.0 to 100.0 A
Corresponding channel setting: 1 to 20 channels (Same channel can be set)
Alarm output: This module outputs alarm status to the H-PCP module as data.
Self-diagnostic
Check item: RAM check
Watchdog timer
Operation at error occurrence in self-diagnosis:
FAIL lamp lights
Reset state
General specifications
Dimensions: 24 (W) 96 (H) 100 (D) mm
Weight: 120 g