8. SPECIFICATIONS
IMSRM15-E6
149
Temperature alarm function
Number of alarms: 2 points
Alarm types: Process high alarm
Process low alarm
Process high alarm (with alarm hold)
Process low alarm (with alarm hold)
The alarm type can be selected for each alarm.
(Alarm action is specified for the H-PCP module)
Setting range: Same as input range: Process high alarm, Process low alarm,
Process high alarm (with alarm hold),
Process low alarm (with alarm hold)
The alarm type can be selected for each alarm.
Setting resolution: Same as input resolution
Alarm output: This module outputs alarm status to the H-PCP module as data.
Self-diagnostic
Check item: RAM check
Adjustment data check
Input value check
Watchdog timer
Operation at error occurrence in self-diagnosis:
FAIL lamp lights
All channel control outputs are turned off.
Reset state
General specifications
Dimensions: 24 (W) 96 (H) 100 (D) mm
Weight: 140 g