Temperature alarm function
Number of alarms: 2 points
Alarm types:
Deviation high alarm Process high alarm
Deviation low alarm Process low alarm
Deviation high/low alarm Process high alarm (with alarm hold)
Deviation band alarm Process low alarm (with alarm hold)
Deviation high alarm (with alarm hold) Deviation high alarm (with alarm re-hold)
Deviation low alarm (with alarm hold) Deviation low alarm (with alarm re-hold)
Deviation high/low alarm (with alarm hold) Deviation high/low alarm (with alarm re-hold)
Specify when ordering (Alarm action is specified for the H-PCP module.)
Setting range: -span to +span: Deviation high alarm, Deviation low alarm,
Deviation high alarm (with alarm hold),
Deviation low alarm (with alarm hold)
0 to span: Deviation high/low alarm, Deviation band alarm,
Deviation high/low alarm (with alarm hold)
Same as input range: Process high alarm, Process low alarm,
Process high alarm (with alarm hold),
Process low alarm (with alarm hold)
Specify when ordering (Alarm action is specified for the H-PCP module.)
Setting resolution: Same as input resolution
Alarm output: This module outputs alarm status to the H-PCP module as data.
Loop break alarm function
Setting range: LBA setting time: 1 to 7200 seconds
LBA deadband (LBD): Same as input range
(LBD is automatically as the value of two times of integral value after the
completion of autotuning.)
Alarm output: This module outputs alarm status to the H-PCP module as data.
Self-diagnostic
Check item: RAM check
Adjustment data check
Input value check
Watchdog timer
Operation at error occurrence in self-diagnosis:
FAIL lamp lights
All channel control outputs are turned off.
Reset state