8. SPECIFICATIONS
IMSRM15-E6
145
Setting range
Set value (SV): Same as input range
Proportional band: 0.1 to 1000.0 % of span
Integral time: 1 to 3600 seconds
Derivative time: 1 to 3600 seconds (PI control when set to 0 second)
Control response parameter: Slow, Medium and Fast (3-step selection)
Neutral zone: 0.1 to 10.0 % of motor driving time
(The time does not become less than 50 ms.)
The output is not turned on until the accumulated value of the
control computation result becomes the neutral zone value or more.
Integrated output limiter: 100.0 to 200.0 %
When Open (Closed) is output in succession, its output is
accumulated. If the accumulated value reaches the set value of the
accumulated output limiter, the Open output is not turned on,
hereafter.
However, if Closed (Open) is output once, the accumulated output is
reset.
Control output
Relay contact output: Rating: 250 V AC, 3 A (Resistive load)
Electrical life: 300,000 times or more (Rated load)
Contact type: 1a contact
Cycle: 1 to 100 seconds variable
Feedback resistance input
Input type: Feedback resistance input from control motor
(O: Open, W: Wiper, C: Closed)
Only input display. (No relation with control.)
Input resistance value: 135
standard
Can specify any one of 100
, 500 , 1 k , 5 k and 10 k
Specify when ordering
Display at input break: Displayed from -199.9 to +199.9 %
Manual output is impossible at input abnormality.
Input sampling: 1 second
Input range: 0.0 to 100.0 % (Full open to full closed)
Adjustable
(Motor driving time can be also automatically set during adjustment)