Instruction manual
8. SPECIFICATIONS
IMSRM15-E6
141
Setting range
Set value (SV): Same as scaling range
Proportional band: 0.1 to 1000.0 % of span
Integral time: 1 to 3600 seconds
Derivative time: 1 to 3600 seconds (PI control when set to 0 second)
Control response parameter: Slow, Medium and Fast (3-step selection)
Proportioning cycle: 1 to 100 seconds
Control output
Relay contact output: Rating: 250 V AC, 3 A (Resistive load)
Electrical life: 300,000 times or more (Rated load)
Contact type: 1a contact
Cycle : 1 to 100 seconds variable
Voltage pulse output: Rating: 0/12 V DC
Allowable load resistance: 600
or more
Cycle : 1 to 100 seconds variable
Current output: Output current: 0 to 20 mA DC and 4 to 20 mA DC
Specify when ordering
Resolution: 11 bits or more
Allowable load resistance: 500
or less
Output impedance: 5 M
or more
(Output minus terminals cannot be connected in common.)
Voltage output: Output voltage: 0 to 1 V DC, 0 to 5 V DC, 0 to 10 V DC and
1 to 5 V DC
Specify when ordering
Resolution: 11 bits or more
Allowable load resistance: 1 k
or more
Output impedance: 0.1
or less
(Output minus terminals can be connected in common only for an output of
1 to 5 V DC.)
Triac output: Capacity: 0.5 A (At an ambient temperature of 40
C)
Zero-cross method
Maximum load voltage: 250 V AC
Open collector output: Load voltage: 12 to 24 V DC
Maximum load current: 100 mA
Leak current when OFF: 0.1 mA or less
Maximum voltage drop at ON: 2.4 V or less (At a load current of 100 mA)
0.7 V or less (At a load current of 10 mA)
The minus terminals of the output with the two channels specification are
internally contacted in common.