Instruction manual
8. SPECIFICATIONS
IMSRM15-E6
139
Self-diagnostic
Check item: RAM check
Adjustment data check
Input value check
Watchdog timer
Operation at error occurrence in self-diagnosis:
FAIL lamp lights
All channel control outputs are turned off.
Reset state
Manual setting function
Auto/Manual transfer: Either Auto or Manual control can be selected.
Setting range: -5.0 to +105.0 %
Balanceless bumpless: Balanceless bumpless transfer between Auto and Manual (both directions).
General specifications
Dimensions: 24 (W) 96 (H) 100 (D) mm
Weight: 120 g