Instruction manual
8. SPECIFICATIONS
IMSRM15-E6
135
Heater break alarm function (Only for H-TIO-A, C and D type) [Optional]
Number of inputs: 1 point/control loop
Setting range: 0.0 to 100.0 A
Accuracy of heater current measurement:
5 % of input value or
2 A (The value whichever is greater)
Input current: 0 to 30 A: CTL-6-P-N
0 to 100 A: CTL-12-S56-10L-N
Current transformer: CTL-6-P-N, CTL-12-S56-10L-N
Specify when ordering
Input rating: Maximum current: 130 mA
Input impedance: 10
Alarm output: This module outputs alarm status to the H-PCP module as data.
Loop break alarm function
Setting range: LBA setting time: 1 to 7200 seconds
LBA deadband (LBD): Same as input range
(LBD is automatically as the value of two times of integral value after the
completion of autotuning.)
Alarm output: This module outputs alarm status to the H-PCP module as data.
Self-diagnostic
Check item: RAM check
Adjustment data check
Input value check
Watchdog timer
Operation at error occurrence in self-diagnosis:
FAIL lamp lights
All channel control outputs are turned off.
Reset state
Manual setting function
Auto/Manual transfer: Either Auto or Manual control can be selected.
Setting range: -5.0 to +105.0 %
Balanceless bumpless: Balanceless bumpless transfer between Auto and Manual (both directions).
General specifications
Dimensions: H-TIO-A, B, C, P: 24 (W) 96 (H) 100 (D) mm
H-TIO-D: 48 (W)
96 (H) 100 (D) mm
Weight: H-TIO-A, B, C, P: 120 g
H-TIO-D: 240 g