8. SPECIFICATIONS
IMSRM15-E6
134
Temperature alarm function
Number of alarms: 2 points
Alarm types:
Deviation high alarm Process high alarm
Deviation low alarm Process low alarm
Deviation high/low alarm Process high alarm (with alarm hold)
Deviation band alarm Process low alarm (with alarm hold)
Deviation high alarm (with alarm hold) Deviation high alarm (with alarm re-hold)
Deviation low alarm (with alarm hold) Deviation low alarm (with alarm re-hold)
Deviation high/low alarm (with alarm hold) Deviation high/low alarm (with alarm re-hold)
Specify when ordering (Alarm action is specified for the H-PCP module.)
Setting range: -span to +span: Deviation high alarm, Deviation low alarm,
Deviation high alarm (with alarm hold),
Deviation low alarm (with alarm hold)
0 to span: Deviation high/low alarm, Deviation band alarm,
Deviation high/low alarm (with alarm hold)
Same as input range: Process high alarm, Process low alarm,
Process high alarm (with alarm hold),
Process low alarm (with alarm hold)
Specify when ordering (Alarm action is specified for the H-PCP module.)
Setting resolution: Same as input resolution
Alarm output: This module outputs alarm status to the H-PCP module as data.
Alarm output (Only for H-TIO-A type) [Optional]
Number of outputs: 1 point
Select any of temperature alarm output 1 (ALM1), temperature alarm output 2
(ALM2), heater break alarm output (HBA) or loop break alarm output (LBA).
Relay contact output: Rating: 250 V AC 24 V DC 2 A (Resistive load)
Electrical life: 300,000 times or more (Rated load)
Contact type: 1a contact
Minimum switching voltage and current: 5 V DC 1 mA
Isolation method: Photocoupler isolation