Instruction manual
8. SPECIFICATIONS
IMSRM15-E6
132
8.2 H-TIO Module
8.2.1 Temperature control module (H-TIO-A, B, C, D, P)
Input
Number of inputs: 1 channel or 2 channels
Isolated between each channel and between input and output
Input type: Thermocouple input: K, J, R, S, B, E, T, N, PLII,
W5Re/W26Re, U, L
RTD input: JPt100, Pt100
Specify when ordering
Input range: Refer to Input range table (P. 14)
Specify when ordering
Resolution: 1
C ( F) or 0.1 C ( F)
Sampling cycle: 0.5 seconds
Signal source resistance effect: Approx. 0.35
V/ (Only for thermocouple input)
Input impedance: 1 M
or more (Only for thermocouple input)
Sensor current: Approx. 0.25 mA (Only for RTD input)
Allowable influence of input lead: 20
or less (Only for RTD input)
Input filter: First order lag digital filter
Time constant: Settable from 1 to 100 seconds
(Setting 0: Filter off)
PV bias: -5.00 to +5.00 % of span
Action at input break: Upscale
Performance
Measured accuracy: 0.3 % of span 1 digit
However, the accuracy of a thermocouple B type input of
0 to 399
C (0 to 799 F) is not guaranteed.
Cold junction temperature compensation error:
Within
1.0 C (Range of 0 to 50 C)
Within
2.0 C between -100 to -150 C
Within
3.0 C between -150 to -200 C
Only for thermocouple input
Control action
Control method: ON/OFF action (Only for H-TIO-A and B types)
Brilliant PID control (PI control can also be used.)
Control cycle: 0.5 seconds
Other functions: Overshoot prevention function (RFB limiter method)
Enhanced autotuning function (Excluding H-TIO-C and D types)
Fuzzy function (Only for H-TIO-P type)