Instruction manual

128
IMSRM15-E6
8. SPECIFICATIONS
8.1 H-PCP Module
Basic functions
Data supervision: Operating and system data
Control unit diagnosis: Function modules configuration check
Self-diagnostic: Check item: ROM/RAM check, Watchdog timer and
CPU power supply monitoring
If error occurs in self-diagnosis, the hardware will automatically
return the module outputs to the OFF position.
Memory backup:
Module with non-volatile memory*:
Backed up by non-volatile memory (FeRAM)
Number of writing: Approximately ten billion times
Depending on storage and operating conditions.
Data storage period: Approximately 10 years
Module with lithium battery*:
Lithium battery for RAM backup, approximate 10 years life for
data retention.
*
To distinguish your module between the above two types, please contact RKC
office or the agent.
Power input
Power supply voltage: 90 to 132 V AC (50/60 Hz) [Including power supply voltage variation]
(Rating: 100 to 120 V AC)
180 to 264 V AC (50/60 Hz) [Including power supply voltage variation]
(Rating: 200 to 240 V AC)
21.6 to 26.4 V DC [Including power supply voltage variation]
(Rating: 24 V DC)
Specify when ordering
Power consumption: H-PCP-A: 100 to 120 V AC: 20 VA max. 24 V DC: 30 W max.
200 to 240 V AC: 20 VA max.
H-PCP-B: 100 to 120 V AC: 25 VA max. 24 V DC: 30 W max.
200 to 240 V AC: 25 VA max.
CE/UL/cUL (or CSA) approved instrument:
100 to 120 V AC: 40 VA max. 24 V DC: 21 W max.
200 to 240 V AC: 50 VA max.
Surge current: 30 A or less
Power output (For function modules)
Output voltage/current: H-PCP-A: 5 V DC: 1.6 A max. 12 V DC: 0.4 A max.
H-PCP-B: 5 V DC: 1.6 A max. 12 V DC: 1.0 A max.
CE/UL/cUL (or CSA) approved instrument:
5 V DC, 1.7 A max. 12 V DC, 1.0 A max.
Must be used within the maximum power consumption value.
Overcurrent protection: Fold-back limiting method: 5 V