Instruction manual
7. FUNCTIONS
IMSRM15-E6
120
Deviation low alarm
When the deviation [Measured value (PV) - Set value (SV)] is the alarm set value or less, the alarm
status is set up.
When the deviation is on the positive side When the deviation is on the negative side
Measured value (PV)
Set value (SV)
Set value (SV)
A
larm
set value
Time
Deviation
Time
OFF OFFON
OFFON ON
Measured value (PV)
Measured value (PV)
Measured value (PV)
A
larm
set value
A
larm status
A
larm status
Deviation
Deviation high/low alarm
When the absolute deviation | Measured value (PV) - Set value (SV) | is the alarm set value or
more/less, the alarm status is set up.
Set value (SV)
Time
OFF
OFF
ON ON
Measured value (PV)
Measured value (PV)
Alarm set value
Alarm set value
Deviation
Deviation
A
larm status
Band alarm
When the absolute deviation | Measured value (PV) - Set value (SV) | is within the alarm set values,
the alarm status is set up.
Time
ON OFF
Measured value (PV)
Measured value (PV)
Set value (SV)
Alarm set value
Alarm set value
Deviation
Deviation
A
larm status