Instruction manual
7. FUNCTIONS
IMSRM15-E6
117
(7) Cascade control
Cascade control monitors the controlled object temperature in the master unit and then corrects the set
value in the slave unit depending on the deviation between the target value (set value) and actual
temperature. The slave unit controls the non-controlled object. As a result, this control matches the
controlled object temperature to the target value.
This cascaded control is suitable when there is a large time lag between the heat source (heater) and
section whose temperature is necessary to be stabilized.
Cascade gain/Cascade bias
The conversion rate when the manipulated output (%) in the master channel is converted to the
relevant cascade signal (
C) can by changed from 0.0 to 100.0 % by the cascade gain.
The cascade bias is a bias added to the input value on the slave side for sensor correction, etc.
(8) Enhanced autotuning
The enhanced autotuning function is used to automatically measure, calculate and set the optimum
PID constants centering around the temperature set value. This function can start from any state after
power on, during a rise in temperature or in stable control. In addition, the AT bias can be set.
AT bias
The AT bias is set when the autotuning function in which the measured value (PV) does not exceed
the set value (SV) is activated. Our autotuning method performs ON/OFF control centering around the
set value (SV), then calculates and sets each of the PID constants by hunting the measured value (PV).
However, overshooting caused by this hunting may not be preferable depending on the controlled
object. In such a case, the desired AT bias is set.
If it is set, another set value (SV) to activate the autotuning function [AT point] can be set.
When AT bias is set to the minus (-) side
Measured value (PV)
Set value (SV)
AT point
A
T bias
Time