Instruction manual

1. OUTLINE
IMSRM15-E6
5
For the H-PCP-A module with the MEMOBUS communication, special specification code
“Z-1001” must be specified at the end of the model code. The H-TIO-K, H-CIO-A,
H-DI-A/B, H-DO-A/B/C/D, H-AI-A/B and H-AO-A/B module cannot be used to the
H-PCP-A module with the specification of MEMOBUS communication.
For the contents of the DO, four functions can be selected out of the six functions; first alarm,
second alarm, heater break alarm, burnout alarm, temperature rise completion and loop break
alarm. For details on the DO Allocation, refer to the following Initial Code.
Initial Code
(1) Digital output 1 (DO1) (5) TI alarm 1
N: Unused N: No alarm function
: Refer to DO allocation code table : Refer to TI, AI alarm code table
(2) Digital output 2 (DO2) (6) TI alarm 2
N: Unused N: No alarm function
: Refer to DO allocation code table : Refer to TI, AI alarm code table
(3) Digital output 3 (DO3) (7) AI alarm 1
N: Unused N: No alarm function
: Refer to DO allocation code table : Refer to TI, AI alarm code table
(4) Digital output 4 (DO4) (8) AI alarm 2
N: Unused N: No alarm function
: Refer to DO allocation code table : Refer to TI, AI alarm code table
DO allocation code table TI, AI alarm code table
1: Temperature alarm 1 H: Process high alarm
2: Temperature alarm 2 J: Process low alarm
3: Heater break alarm K: Process high alarm (with alarm hold)
4: Burnout alarm L: Process high alarm (with alarm hold)
5: Temperature rise completion
6: AI alarm 1
7: AI alarm 2
8: Loop break alarm
(TI alarm output is common
with temperature alarm output)
For DO1 to DO4, specify different code numbers other than “N.”
For type B, only DO1 or DO2 can be selected. For DO3 or DO4, set “N.”
- - -
(1) (2) (3) (4) (5) (6) (7) (8)