Instruction manual

7. COMMUNICATION DATA LIST
IMR01Y06-E6
66
Continued from the previous page.
Extension
number
Communication item
Attri-
bute
Data range
Factory
set value
152
Heater break determination
point 2
R/W
0.0 to 100.0 % of HBA2 set value
(0.0: Heater break determination is invalid)
If there is no Current transformer 2 (CT2) or
CT2 is assigned to “0: None,” set to RO (Read
only data).
If Heater break alarm 2 (HBA2) corresponds
to “0: Type A,” set to RO (Read only data).
30.0
153
Heater melting
determination point 2
R/W
0.0 to 100.0 % of HBA2 set value
(0.0: Heater melting determination is invalid)
If there is no Current transformer 2 (CT2) or
CT2 is assigned to “0: None,” set to RO (Read
only data).
If Heater break alarm 2 (HBA2) corresponds
to “0: Type A,” set to RO (Read only data).
30.0
154 Unused
y
y
y
159
160
Display unit
R/W
0: °C
1: °F
Use to select the temperature unit for
Thermocouple (TC) and RTD inputs.
Based on
model code.
When not
specifying: 0
161
Input scale high
R/W
TC/RTD inputs:
Input scale low to Maximum value of the
selected input range
Voltage (V)/Current (I) inputs:
19999 to +19999
Varies with the setting of the Decimal point
position selection.
TC/RTD:
Maximum
value of the
selected
input range
V/I: 100.0
162
Input scale low
R/W
TC/RTD inputs:
Minimum value of the selected input range
to Input scale high
Voltage (V)/Current (I) inputs:
19999 to +19999
Varies with the setting of the Decimal point
position selection.
TC/RTD:
Minimum
value of the
selected
input range
V/I: 0.0
163
Input error determination
point (high)
R/W
Input scale low
(5 % of input span) to
Input scale high + (5 % of input span)
Varies with the setting of the Decimal point
position selection.
TC/RTD:
Input scale
high + (5 %
of input span)
V/I: 105.0
164
Input error determination
point (low)
R/W
TC/RTD:
Input scale
low (5 %
of input span)
V/I: 5.0
Continued on the next page.