User`s manual

Temperature Controller MODBUS SIO Driver
GP-Pro EX Device/PLC Connection Manual
12
Device Setting
To display the setting screen, click ([Setting]) of the External Device you want to set from [Device-Specific
Settings ] of [Device/PLC Settings ].
Settings of External Device
Use the SET key, shift key, down key and up key on the front of the Temperature Controller for communication
settings of the External Device.
Please refer to the manual of the Temperature Controller for more details.
Procedure
1. While pressing down the SET key, press and hold the shift key to move from the PV/SV display mode to the
engineering mode.
2. Press the up key several times to specify F60, and press the SET key.
3. Set 1 for CMP1.
4. While pressing down the SET key, press the shift key to move from the engineering mode to the PV/SV
display mode.
5. While pressing down the SET key, press the shift key to move from the PV/SV display mode to the setup
setting mode.
6. Press the SET key several times to select the parameter.
7. Press the down/up keys to change the setting.
8. While pressing down the SET key, press the shift key to move from the setup setting mode to the PV/SV
display mode.
9. To confirm the setting, restart the Temperature Controller.
Setting Value
Add1 1
bPS1 9.6
bIT1 8n1
Parameters to be set vary depending on the Temperature Controller. Please refer to the manual of
the Temperature Controller for more details.