1. SPECIFICATIONS
Interface
: Based on RS-485, EIA standard
Connection method
: 2-wire system, half-duplex multi-drop connection
Communication distance:
1 km max.
The maximum communication distance will be affected by
the surrounding conditions.
Synchronous method
: Start/stop synchronous type
Communication speed:
2400 bps, 4800 bps, 9600 bps, 19200 bps
Data bit configuration:
Start bit: 1
Data bit: 7 or 8
Parity bit: Without, Odd or Even
Stop bit: 1 or 2
Protocol:
ANSI X3.28 subcategory 2.5, A4
Polling/selecting type
Error control :
Vertical parity (With parity bit selected)
Horizontal parity (BCC check)
Communication code:
ASCII 7-bit code
Termination resistor:
Externally connected
Xon/Xoff control:
None
Maximum connections:
32 instruments maximum including a host computer
Signal logic:
RS-485
Signal voltage Logic
V (A) - V (B) 2 V 0 (SPACE)
V (A) - V (B) -2 V 1 (MARK)
Voltage between V (A) and V (B) is the voltage of (A) terminal for
the (B) terminal.