Installation guide

GP-PRO/PBIII for Windows Ver. 6.1 PLC Connection Manual
Chapter 12 - Indicating Controllers
12-4-6
12.4 RKC INSTRUMENT INC. Controllers
SR-Mini Series
Up to 16 SR-Mini Series modules can be connected to a single
GP/GLC/LT.
If a communications cable is used, be sure to connect its SG (sig-
nal ground) terminal.
RS-232C cables should be 15 meters or less.
RS-422 (2-wire) cables should be 500 meters or less.
The following RS-422 cables are recommended for SR-Mini Se-
ries units.
Company Type Comments
RKC
INSTRUMENT INC.
W-BF-01- XXXX
*1
Used when connecting an
SR-Mini to a LT/GLC/GLC
RKC
INSTRUMENT INC.
W-BF-02- XXXX
*1
Used when connecting an
SR-Min to an SR-Mini
*1 XXXX indicates the cable length (mm).
!!
!!
!
Important
REX-F Series
Up to 31 REX-F Series units can be connected to a single GP/
GLC/LT.
Connect the shield to the GP/GLC/LT's FG terminal.
If a communications cable is used, be sure to connect its SG (sig-
nal ground) terminal.
RS-232C cables must be 15 meters or less.
RS-422 cables must be 600 meters or less.
With REX-F Series units, the terminal numbers and signal names
will vary, depending on the unit's model type and data transfer
method used. The following tables show the possible model type
and signal name combinations.
!!
!!
!
Important