Installation guide
GP-PRO/PBIII for Windows Ver. 6.1 PLC Connection Manual
Chapter 12 - Indicating Controllers
12-4-20
12.4 RKC INSTRUMENT INC. Controllers
If the address designation method and the Indicating Controller data's decimal point
position are not the same, the address' decimal data will be either cut off or replaced
with "0".
Please refer to your RKC Instrument Inc. Indicating Con-
troller installation guide for information about identifier data
setting ranges and decimal point positions.
EX. 1) When writing "100.0" to the CB Series unit's Alarm 1 Setting (A1)
GP/GLC/LT's address value: 0x1007
GP/GLC/LT's write value: 1000
EX. 2) When writing "100" to the CB Series unit's Alarm 1 Setting (A1)
GP/GLC/LT's address value: 0x0007
GP/GLC/LT's write value: 100
Depending on the Address designation method used, the Indicating
Controller's write data will be as follows:
No change to
Address data
Adding 0x1000 to
the Address
Adding 0x2000 to
the Address
Adding 0x3000 to
the Address
1 1 0.1 0.01 0.001
123 123 12.3 1.23 0.123
1234 1234 123.4 12.34 1.234
Indicating Controller Data
GP/GLC/LT Data