7. INITIAL SETTING
Parameters in the Initialization mode should be set according to the application before setting any parameter
related to operation. Once the Parameters in the Initialization mode are set correctly, those parameters are not
necessary to be changed for the same application under normal conditions. If they are changed unnecessarily,
it may result in malfunction or failure of the instrument. RKC will not bear any responsibility for malfunction or
failure as a result of improper changes in the Initialization mode.
7.1 Go to Initialization Mode
1. Turn on the power to this controller. The instrument goes to
the PV/SV display after confirming input type symbol and
input range.
2. Press the SET key for two seconds to go to the Parameter
Setting Mode from the PV/SV display.
3. Press the SET key until “LCK” (Set Data Lock display) will be
displayed.
4. The high-lighted digit indicates which digit can be set. Press
<R/S key to high-light the thousands digit.
(The section in
each image of the controller shows the digits which are not
high-lighted.)
Set data lock function display
SV
CB100
AT
SET R/S
OUT1 OUT2 ALM1 ALM2
PV
5. Press the UP key to change 0 to 1.
SV
CB100
AT
SET R/S
OUT1 OUT2 AL M1 ALM2
PV
6. Press the SET key to store the new set value. The display
goes to the next parameter, and the Initialization mode is
unlocked.
CT1 input value display
SV
CB100
PV
AT
SET R/S
OUT1 OUT2 AL M1 ALM2
7. Press the <R/S key for two seconds while pressing the SET
key to go to the Initialization Mode. When the controller goes
to the Initialization Mode, “Cod” will be displayed.
Initialize code selection display
of initialization mode
SV
CB100
PV
AT
SET R/S
OUT1 OUT2 AL M1 ALM2
CT1 input value display
SV
CB100
PV
AT
SET R/S
OUT1 OUT2 ALM1 ALM2
Cod SL1 (Input type selection) See P. 10
0000 SL2 (Temperature unit and cooling type selection) See P. 10
SL4 (Alarm 1 type selection) See P. 10
SL5 (Alarm 2 type selection) See P. 10
SL11 (SV alarm type selection) See P. 11
Cod SLH (Setting limiter [high]) See P. 11
0001 SLL (Setting limiter [low]) See P. 11
PGdP (Decimal point position) See P. 11
7.2 Exit Initialization Mode
When any parameter setting is changed in the Initialization
Mode, check all parameter set values in SV Setting Mode
and Parameter Setting Mode.
1. Press the <R/S key for two seconds while pressing the SET
key from any display in the Initialization Mode. The controller
goes back to the operation mode and the PV/SV display will
be displayed.
2. Press the SET key for two seconds in the PV/SV display.
3. Press the SET key until “LCK” (Set Data Lock display) will be
displayed.
4. The high-lighted digit indicates which digit can be set. Press
<R/S key to high-light the thousands digit.
(The section in
each image of the controller shows the digits which are not
high-lighted.)
5. Press the DOWN key to change 1 to 0.
Set data lock function display
SV
CB100
AT
SET R/S
OUT1 OUT2 ALM1 ALM2
PV
6. Press the SET key to store the new set value. The display
goes to the next parameter, and the Initialization mode is
locked.
CT1 input value display
SV
CB100
PV
AT
SET R/S
OUT1 OUT2 AL M1 ALM2
7.3 Initial Setting Menu
The “Cod” display will be displayed when the controller goes to
the Initialization Mode.
Set value
0: Initialization mode
locked
1: Initialization mode
unlocked
The parameter displayed
varies on the instrument
specification.
WARNING
!
The parameter displayed
varies on the instrument
specification.
Do not change to any parameter in the Initialization Mode
which is not described in the initial setting menu above.
It may result in malfunction or failure of the instrument.
Press the <R/S key while pressing the SET
key for 2 seconds with the unlocked.
PV/SV display mode or Parameter setting mode
Initialization code selection
To PV/SV display mode
To PV/SV
display mode
A
larm1 type selection
Input type selection
(SL1)
(SL4)
(SL5)
A
larm2 type selection
(SL11)
SV alarm type selection
Temperature unit and
cooling type selection
(SL2)
Set Cod to 0000. Set Cod to 0001.
(Cod)
Setting limiter
[low]
(SLH)
(SLL)
Setting limiter
[high]
Decimal point
position
(PGdP)
Initialization code selection
: Press the SET key, or press the SET key several times.
: Press the <R/S key while pressing the SET key for 2 seconds.