8. TROUBLESHOOTING
IMCB14-E1
36
Continued from the previous page.
Symptom Probable cause Solution
Error code 1 Function code error
(An unsupported function code was
specified)
Confirm the function code
Error code 2 Written to read only data. Confirm the address of holding
register
Any address other than 0000H to 0019H
is specified.
PID constants or anti-reset windup
(ARW) data are set to 0 and 1 is entered
at self-tuning (ST) function
Set the PID constants and anti-reset
windup (ARW) data to any number
other than 0.
Either one of PID constants and anti-reset
windup (ARW) data are written during
execution of the self-tuning (ST) function.
Set the self-tuning (ST) function to 0.
Error code 3 The data written exceeds the setting
range.
Confirm the setting data
When the specified number of data items
in the query message exceeds the
maximum number of data items available.
Re-set the data within the range of 1
to 125 (0000H to 007DH).
Error code 4 Self-diagnostic error Turn off the power to the instrument.
If the same error occurs when the
power is turned back on, contact your
nearest RKC sales office or agent.
Error codes 1 to 4 indicate that an error response message has been transmitted.